Three Phase Oil Filled Distribution Transformer

Three Phase Oil Filled Distribution Transformer

500 KVA three phase Oil Filled Distribution Transformer is popular in the United States, Canada, Mexico, Indonesia, Australia, Thailand, Vietnam and other countries. It is very suitable for public power facility transformation and industrial and commercial applications.
Send Inquiry
Chat Now

Have questions? GNEE sales representatives are available for live chat now

Send E-mail: sales@gneeelectric.com

Tel: +8615824687445

The three-phase oil-filled distribution transformer adopts the latest new technology and process to effectively reduce no-load loss (≤480W) and load loss (≤3650W). The transformer has a compact structure, low temperature rise, good heat dissipation, and is safe and reliable. The improvement of design process and material has increased the service life of the transformer. The short-circuit resistance performance meets the IEC 60076 standard and is widely used in power supply and distribution systems below 35kV in substations, power stations, power plants, industrial and mining enterprises, etc., to meet the power distribution needs of various users.

Technical specifications

500 KVA Three Phase Oil Filled Distribution Transformer Specification and Data Sheet

Place of Origin China
Brand Name GNEE Transformer
Model Number Oil immersed transformer
Type Distribution Transformer
Standard IEC60076
Certificate CSA SGS CE UL cUL
Rated Power 500 KVA
Frequency 50 HZ/60 HZ
Phase Three
Cooling Type ONAN
Primary Voltage 11 KV
Secondary Voltage 0.415 KV
Winding Material Aluminum/Copper
Vector Group Dyn11,Yyn0,Yzn11
Oil preservation Hermetically Sealed/ Conservator/ Free Breathing
Dielectric liquids Mineral oil / Dimethyl Silicone/ FR3 oil
Coolers corrugated wall or radiator
Impedance 0.04
Tap Changer NLTC
Tapping Range ±2*2.5%
Operating temperature 40 To+180
No Load Loss 0.48KW
On Load Loss 3.65KW
Accessories Standard Configuration
Remarks N/A

3 phase distribution transformer

Three-Phase Oil-Immersed Distribution Transformer Partial Inspection
  • Certificate Verification: Verify the transformer's certificate. If the certificate is older than two months, retest the insulation resistance to ensure it meets the required standards.
  • Insulation Test: Test the insulation resistance using a megohmmeter to confirm insulation integrity; perform a dielectric absorption ratio (DAR) test to assess insulation condition.
  • Oil Level and Quality: Check the oil level and ensure the vents are unobstructed. There should be no signs of oil leakage; sample the transformer oil and analyze its dielectric strength, moisture content, acidity, and dissolved gas analysis (DGA) to detect potential problems such as overheating or arcing.
  • Insulation and Connections: Check the high and low voltage bushings and associated wires for signs of damage; ensure all screws and connections are tight to prevent electrical faults. Use infrared thermography to detect hot spots at connection points, which may indicate loose connections or corrosion.
  • Tap Changers and Fuses: Confirm that the tap changer position is properly set as per the operating requirements. Inspect and clean the tap changer contacts and mechanism, and perform electrical tests to ensure proper operation.
  • Lightning protection and grounding: Check lightning arresters for signs of damage; measure ground resistance to confirm it meets safety standards, and verify the integrity of ground connections and electrodes.
  • Cooling system: Check radiators and cooling fans to ensure they are clean and operating properly. Check the operation of the oil circulation pump (if equipped) to ensure effective cooling.
  • Noise and vibration: Monitor the transformer for any unusual noise or vibration, as this may indicate an internal problem.
application case

Pole mounted distribution transformer

Package&Delivery

Pad mounted distribution transformers

Hot Tags: three phase oil filled distribution transformer, China three phase oil filled distribution transformer manufacturers, suppliers, factory, Amorphous Core Type Distribution Transformer, Single Phase Oil Filled Transformers, 1000 kva compact substation, 25 kva distribution transformer, Oil Filled Current Transformer, Oil Immersed Distribution Transformer