200KVA 3-Phase hermetically sealed oil immersed distribution transformers technical specification
Nov 10, 2025
Leave a message
A 200 kVA transformer is one of the types of transformers used to transfer large amounts of electrical energy over long distances.
| Description | Unit | Particulars |
|---|---|---|
| Rated Power | KVA | 200 |
| HV & LV winding material | Copper | |
| Applied Standard | IEC 60076 | |
| Primary Voltage | KV | 20 |
| Secondary Voltage (at No-load) | KV | 0.4 |
| Rated Primary Current | A | 5.77 |
| Rated secondary current | A | 288.68 |
| Frequency | Hz | 50 |
| Vector Group | Dyn11 | |
| Voltage Regulation | % | ±2 * 2.5% |
| Maximum Ambient Temperature | °C | 50 |
| Maximum Temperature Rise for oil | °C | 50 |
| Maximum Temperature Rise for winding | °C | 55 |
| No-load losses | (W) | 500 |
| Copper losses (at 75 °C) | (W) | 2400 |
| Impedance Voltage (IEC Tolerance Applied) | % | 4 |
| Transformer Type | Hermetically Sealed | |
| Cooling Method | ONAN | |
| Weight of oil | kg | 180 |
| Total weight of transformer | kg | 1020 |
| Over all Dimensions Length x Width x Height | mm | 1260 x 825 x 1390 |
Tolerance in dimensions and weights ±10 %

We generally manufacture distribution transformers in this power range, mainly in two different types :
-
Transformer with conservator tank (WCT),
-
Hermetically sealed type (HST),
Meanwhile here is the advantage-disadvantage of the WCT-HST types :
In HST type, tank pressure is more than WCT type.
WCT type generally works under low pressure due to its open to atmosphere,
In HST type, cooling/insulation oil does not contact to the air (theoretically).
Therefore oil maintenance period is longer than WCT type,
HST type transformers and their related parts generally work under higher temperature
(If we evaluate WCT-HST work under same conditions).
What are the specifications of 200 kva transformer?
A 200 kVA transformer is a phase-3 type of transformer. A phase-3 transformer means three sets of primary and secondary windings. Three single-phase transformers conjoined into one. 200 kVA would be the highest capacity it can contain, and the wires have to weigh between 495 to 705 kilograms.
This 200kVA 3-Phase Distribution Transformer's primary voltage is 480 volts and a secondary voltage of 240 volts. Its frequency lies around 50 or 60 hertz, and it has both aluminum and copper wires coiled around it. Also, it utilizes a dry air cooling type with a warranty that lasts for a year.
Generally, this 200kVA 3-Phase Distribution Transformer can work around negative fifteen to forty degrees celsius. Additionally, it can also work with a humidity of less than or equal to 90 percent RH, provided no condensation is present in the machine. Finally, it can work properly only if it is placed less than 1 kilometer above sea level.
Is there a 200 kVA transformer?
200 kVA transformer is a typical rated capacity in all types of transforms. GNEE Electric has designed, produced, and tested all kinds of 200 kVA transformers and exports to U.S. and Canada with the CSA, ANSI/IEEE standards.
What is the size of a 200 kVA transformer?
200-KVA
| Description | Unit | Particulars |
|---|---|---|
| Cooling Method | ONAN | |
| Weight of oil | kg | 180 |
| Total weight of transformer | kg | 1020 |
| Over all Dimensions Length x Width x Height | mm | 1260 x 825 x 1390 |
How much load can a 250 kVA transformer handle?
250,000 volt-amperes
A 250 kVA transformer is an electrical device capable of transforming electrical energy from one circuit to another with a maximum power rating of 250 kilovolt-amperes (kVA). This means the transformer is designed to handle a maximum of 250,000 volt-amperes (VA) of electrical power.