Enameled Wires Used in Oil-Immersed Transformer Windings: Grades, Classes and Selection

Oct 21, 2025

Leave a message

How Winding Construction Drives the Conductor Choice

In an oil-immersed transformer the winding conductor has three duties at the same time: it carries rated current with acceptable I2R loss, it holds its geometry against the mechanical forces released by a through-fault, and it survives decades of contact with hot mineral insulating oil. Low-voltage windings on medium and large distribution ratings are normally cylindrical copper foil wound on the core limb, because foil gives a high fill factor and a short thermal path into the oil. Smaller ratings use round enameled wire in one or two layers. High-voltage windings are built as multilayer cylinders or as disc windings so that the ampere-turn distribution stays balanced, leakage flux is small and short-circuit strength is high.

The oil also fixes the design envelope. A sealed corrugated tank absorbs oil expansion through the elasticity of its own walls, so the winding must tolerate a permanently oil-filled environment with no breathing path for moisture. That is why conductor insulation, not the tank, is usually the life-limiting element in a liquid-immersed unit.

Enameled Wire Types Used in Oil-Immersed Windings

Enameled (film-insulated) wire is specified by enamel chemistry and by thermal class, and the grade chosen has to match the winding hot-spot temperature as well as the oil. The grades most often quoted for liquid-immersed distribution and power transformers are listed below.

Conductor / enamel type Thermal class Reference Typical winding use
Polyurethane, solderable 130 / 155 IEC 60317-0-1 Control and auxiliary windings, tap leads
Polyesterimide (EIW) 180 IEC 60317 series LV layer windings; base film under paper on HV conductors
Polyesterimide overcoated with polyamide-imide 200 IEC 60317 series HV windings that need extra thermal margin
Paper-wrapped rectangular copper, enameled core Set by the base enamel IEC 60641 for the paper Disc and layer windings, HV side
Bare copper foil, uncoated Not applicable ASTM B152 LV cylindrical windings, larger distribution units

Class 130 and class 155 soldered grades are effectively confined to low-current auxiliary circuits, where the joint is made by timing rather than by brazing. On the main windings, class 180 and class 200 enamels dominate, because the oil temperature rise under IEC 60076-2 plus the winding gradient leaves little margin for a lower class.

Round Wire, Rectangular Strip and Foil

Round enameled wire is supplied from about 0.50 mm to 3.15 mm in diameter for layer windings; above that size the conductor is normally replaced by rectangular strip so that the winding stays compact and the eddy loss stays low. Rectangular strip is enameled first and then wrapped with kraft paper or pressboard to build the turn-to-turn and layer insulation in one pass. Nominal strip thicknesses in common use run from about 1.0 mm to 5.6 mm with widths from 5 mm to 20 mm, and the paper covering is quoted as a build in tenths of a millimetre on each side.

Copper foil for LV windings is ordered as soft, high-conductivity sheet under ASTM B152, typically 0.5 mm to 2.0 mm thick, with the foil width matched to the winding height so that no helical crossing is required. Foil edges are deburred and the first and last turns are insulated with a wrapped barrier because the turn-to-turn voltage at the foil ends is the highest in the winding.

Insulation System, Oil Compatibility and Incoming Tests

The conductor film is only one element of a composite insulation system, so it is assessed as a system rather than as a wire. The mineral insulating oil should meet IEC 60296 for the class of unit, and the enamel, paper and oil combination has to be checked for compatibility at the design hot-spot temperature: enamel softening, paper ageing and oil oxidation all accelerate when the system is mismatched. Insulating paper and pressboard are specified under IEC 60641.

Winding wire properties are verified with the test methods of IEC 60851, which covers conductor dimensions, enamel thickness, elongation, flexibility and adherence, scrape resistance, dielectric breakdown voltage and thermal endurance. For oil-immersed duty the three results that matter most in an incoming record are dielectric breakdown, enamel adherence after elongation, and the absence of bare or thin spots after winding. Dissolved gas analysis of the oil on a finished unit, interpreted under IEC 60599, is the practical field check that the enamel and paper are not degrading ahead of schedule.

Selection and Receiving Checklist

For each purchase order, fix the grade by its standard designation, not by a trade description: enamel chemistry, thermal class, bare conductor dimensions and tolerance, enamel build, and the applicable part of IEC 60317. Record the packaging method so that spools are protected from moisture and mechanical damage in transit. Confirm that the delivered spool length matches the winding programme, and keep one sample length per batch for elongation and breakdown tests before the wire is released to the winding station.

Frequently Asked Questions

Q: Why is copper foil used instead of enameled round wire on low-voltage windings?
A: Foil gives a much higher copper fill factor for the same winding space and a short radial thermal path into the oil, so the LV winding runs cooler and the unit can be built more compactly. Round wire is retained only on small ratings where foil handling is uneconomic.

Q: What thermal class should be specified for a distribution transformer winding?
A: Class 180 or class 200 enamel is the usual choice for the main windings. Class 130 and class 155 grades are normally reserved for auxiliary and control windings that carry low current and are not exposed to the full winding hot-spot temperature.

Q: Does the enamel alone insulate the high-voltage winding in oil?
A: No. On HV windings the enamel is a base film and the turn and layer insulation is completed by kraft paper or pressboard wrapped over the strip conductor. The enamel protects the conductor surface and limits local discharge, while the paper carries the dielectric duty.

Q: How is winding wire quality verified before winding?
A: Sample lengths are tested with the methods of IEC 60851 for dimensions, enamel thickness, elongation, flexibility and adherence, scrape resistance and dielectric breakdown. Results are recorded against the spool batch so that any later fault can be traced back to a specific delivery.

Q: Which oil specification applies to an oil-immersed transformer?
A: Mineral insulating oil is normally specified to IEC 60296, with the fluid class selected to suit the lowest expected ambient and the sealing system of the tank. Oil condition is then monitored in service through dielectric breakdown and dissolved gas analysis.

Q: Can a class 155 wire be used if the unit is only lightly loaded?
A: It is not recommended. Loading varies over the service life and the winding hot spot, not the average oil temperature, sets the ageing rate. The small saving on wire cost is not worth the loss of thermal margin on a unit expected to run for twenty-five years or more.