Amorphous Alloy Power Transformers
Have questions? GNEE sales representatives are available for live chat now
Send E-mail: sales@gneeelectric.com
Tel: +8615824687445
Amorphous alloy power transformer is a kind of energy-saving transformer, compared with ordinary transformers, amorphous alloy power transformer has the advantages of low no-load loss, low cost, high efficiency, convenient transportation and simple installation. Therefore, in the design process of amorphous alloy power transformer, ensuring no-load loss value and improving the working effect are important core issues. Moreover, when purchasing, in addition to considering that the core of the amorphous alloy power transformer product is not affected by external forces, it is necessary to accurately calculate the reasonable choice of amorphous alloy characteristic parameters.
Working Conditions:
No. |
Conditions |
Units |
Parameter Values |
|
1 |
Pollution Grade |
|
IV |
|
2 |
Ambient Temperature |
Maximum Daily Temperature |
℃ |
40 |
Minimum Daily Temperature |
-45 |
|||
Maximum Daily Temperature Difference |
K |
25 |
||
Average Temperature of the Hottest Month |
℃ |
30 |
||
Maximum Annual Average Temperature |
20 |
|||
3 |
Humidity |
Average Daily Relative Humidity |
% |
≤95 |
Average Monthly Relative Humidity |
≤90 |
|||
4 |
Altitude |
m |
1000 |
|
5 |
Solar Radiation Intensity |
W/cm2 |
0.1 |
|
6 |
Maximum Icing Thickness |
mm |
10 |
|
7 |
Maximum average wind speed: keeping in good conditions for 10min at 10m from the ground level |
m/s |
35 |
|
8 |
Earthquake Resistance |
Horizontal Ground Acceleration |
m/s2 |
2 |
Safety Coefficient of 3 Since Resonance Cycles |
|
≥1.67 |
||
9 |
Installation Site |
|
Outdoor |
|
Note 1: Working conditions in high altitude regions (above 1000m) must be adjusted in conformity with Q/GDW 13001-2014 (High Altitude External Insulation Configuration Technical Specification). |
The structural requirements for amorphous alloy power transformers are as follows:
1, the structure should be safe and reliable, easy to install, easy to maintain, and should be able to withstand the mechanical, electrical and thermal stress in the standard material composition.
2, winding material: high voltage winding is wound with copper wire or copper foil, low voltage winding is wound with copper foil.
3, iron core: the use of soft magnetic characteristics of amorphous alloy strip.
4, core structure: three-phase three columns or three-phase five columns.
5, the cabinet should use strong Angle steel as support.
6, All non-current carrying parts such as the shell and support frame should be connected together and grounded through the ground bus.
Package&delivery
Hot Tags: amorphous alloy power transformers, China amorphous alloy power transformers manufacturers, suppliers, factory, Single Phase Pad Mounted Power Transformer, Dry Type Pad Mounted Transformer, Pole Mounted Single Phase Transformer, cast coil dry type transformer, 2500 kva pad mounted transformer, Cast Dry Type Transformer
You Might Also Like