75 kVA Three-Phase Transformer: Complete Specifications and Dimensions
Jan 13, 2026
Leave a message
What Is a 75 kVA Three-Phase Transformer
A transformer is a passive electrical device that uses electromagnetic induction to transfer electrical energy from a primary circuit to a secondary circuit. A 75 kVA three-phase transformer is a mid-range distribution unit widely used where three-phase power is required but demand stays moderate. Its ability to adjust voltage levels enables efficient distribution and transmission of electrical power between the grid and the load.
Dimensions and Weight
A typical 75 kVA dry three-phase transformer measures approximately 1092 mm high, 610 mm wide, and 508 mm deep, about 43 by 24 by 20 inches. The unit weighs about 500 lb, or 227 kg, in dry-type construction; the oil-filled equivalent weighs approximately 750 lb, about 340 kg, and shipping weight is roughly 550 lb, about 249 kg. Installation requires a forklift or crane, and the floor must support the unit weight, with at least 750 lb recommended. Pre-plan access routes and allow 24 to 48 hours for concrete curing if a new pad is poured.
Full Load Amperage at Various Voltages
For a three-phase transformer, full load amperage is calculated as kVA times 1000 divided by voltage times 1.732. At 120 V the full load current is 360.9 A, at 208 V it is 208.2 A, at 240 V it is 180.4 A, at 277 V it is 156.3 A, at 480 V it is 90.2 A, and at 600 V it is 72.2 A. Wire sizing follows the applicable electrical code ampacity tables with appropriate overcurrent protection.
Electrical Specifications
| Parameter | Value |
|---|---|
| Rated kVA | 75 |
| Frequency | 60 Hz standard, 50 Hz on request |
| No-load loss | 180 W typical |
| Load loss | 700 W at 100 percent load |
| Total losses | 880 W at full load |
| Impedance | 4.5 percent |
| Efficiency | 98.7 percent at full load |
| Sound level | About 41 dB |
When a 75 kVA Three-Phase Transformer Is the Right Choice
The 75 kVA three-phase transformer suits small manufacturing facilities with three-phase equipment, commercial kitchens with three-phase ovens, HVAC systems with compressors up to about 37 HP, elevator and escalator supply, and multi-tenant building common areas. A typical load distribution for a 75 kVA installation might include a three-phase HVAC compressor at 30 kVA, combined three-phase motors at 22 kVA, lighting at 11 kVA, and receptacle loads at 11 kVA; actual loads vary, and a detailed load calculation is always required. Adequate ventilation clearance of at least 3 inches on the sides and 6 inches on top is needed for cooling, and impedance matching is critical when paralleling transformers.
Frequently Asked Questions
Q: What are the dimensions of a 75 kVA transformer?
A: A typical 75 kVA dry three-phase transformer measures about 1092 by 610 by 508 mm, about 43 by 24 by 20 inches.
Q: How much does a 75 kVA transformer weigh?
A: About 500 lb, 227 kg, dry; oil-filled units weigh about 750 lb, 340 kg.
Q: What is the full load amperage at 480 V?
A> 90.2 A for a three-phase 75 kVA transformer, calculated as 75 times 1000 divided by 480 times 1.732.
Q: What loads can a 75 kVA transformer handle?
A: Up to 75 kVA apparent power, equal to about 63.8 kW at 0.85 power factor.
Q: What is the efficiency at full load?
A: About 98.7 percent with total losses of 880 W.
Q: What wire size feeds a 75 kVA transformer?
A: Per the applicable code ampacity tables, a 2 AWG copper conductor is typical for the 115 A primary requirement under standard conditions.
For 75 kVA transformer quotations with your required voltage and configuration, contact our sales team.