Medium Voltage Control Power Transformers (CPTs) are single-phase dry-type transformers used to supply control power in medium voltage switchgear and transformers. They have open construction with an epoxy resin encapsulated coil. Power ratings of 5, 10 and 15kVA with nominal primary voltages range from 2.4kV to 15kV and secondary voltages typically are configured for 120/240V (series parallel) operation. It is supplied with three +/-2.5% taps above and below nominal voltage on the primary winding. For low power losses, the magnetic core is wound with grain-oriented electrical steel, and the high-voltage coil is vacuum encapsulated in epoxy resin. In addition to protecting the coil from moisture and foreign particulate matter, the resin epoxy provides a higher ability to withstand mechanical forces during short-circuits, than standard varnished Vacuum Pressure Impregnation (VPI) or "dip in varnish and then bake" process.
| Capacity | 500VA to 3,000VA Single Phase |
| Voltage Class | up to 7.2kV (45kV BIL) |
| Cooling | Self Cooled (ANN / AN) |
| Frequency | 60Hz (50/60Hz Optional) |
| Conductors | Copper (Cu) Windings |
| Insulation System | 180°C (115°C rise) |
| Enclosure Type | Open Construction With Encapsulated Coil |
| Warranty | 12 Months (See Warranty and Limitations) |
| Quality System | ISO 9001:2015 Quality Management System |
| Certifications |
CSA Certified UL Listed |
| Reference Standards |
CSA C22.2 No 47 CSA C22.2 No 66.1 CSA C9 IEEE C57.13.2 |
| Optional Features & Accessories |
Suitable For 50Hz Nominal Frequency Primary Fuse Clips & Fuses |
Medium Voltage Power Transformers Product features
- Standard sizes: 500VA to 5kVA. Custom sizes may be available.
- 180°C (356°F) insulations system, 115°C (239°F) temperature rise under full load
- 25kV BIL for primary voltages up to 5kV, 35kV BIL for primary voltages over 5kV to 7.2kV
- Standard 48″ leads on primary, terminal block connections on secondary
- 50 Hz and 60 Hz designs available
Reliability Test Equipment

R&D Equipments

Packaging&Shipping

Hot Tags: medium voltage control power transformers, China medium voltage control power transformers manufacturers, suppliers, factory, Amorphous Alloy Metal Core Transformer, Power Substation Transformer, 500 kva compact substation, Power Transformer In Substation, Dry Type Transformers, Three Phase Distribution Transformer