10KV Fully Sealed Three-phase Oil-immersed Power Distribution Transformer

Nov 06, 2025

Leave a message

10kv Oil immersed Transformer Types

For HENAN GNEE ELECTRIC CO., LTD., a 10kv transformer can be a three-phase oil immersed transformer, or a column mounted three-phase oil immersed transformer. These types of transformers have the same principle, but their structures are different, and different types of transformers have different applications. HENAN GNEE ELECTRIC CO., LTD. provides you with the most ideal solution.

  • 10kV three-phase oil immersed transformer (rated voltage 6kV-35kV)
  • Install a three-phase oil immersed transformer (rated voltage 2.4kv-34.5kv) on an 10kV column
news-530-300
  • Compatible with AC 50Hz/60Hz power systems operating up to 20kV.

 

  • Suitable for industries like petroleum, metallurgy, and chemical plants, as well as dusty and challenging environments.

 

  • Ideal for energy distribution in power substations, industrial facilities, and public infrastructure.

 

  • Low maintenance requirements with no need for periodic oil sampling.

With advanced core and winding designs, these transformers deliver low energy loss, excellent cooling, and long service life.The corrugated tank design compensates for oil volume changes caused by temperature fluctuations, improving operational stability.The transformers are sealed to prevent oxygen and moisture ingress, ensuring optimal insulation and oil longevity.Safety features, including pressure release and gas relay options, enhance reliability for critical installations.

 

10kv Oil immersed Transformer Technical Specifications


- Input voltage: 10kV

- Output voltage: 0.4kV 0.415 kv 0.420kv 0.430kv 0.440kv
- Capacity: 30-2500 kva
- Frequency: 50/60 HZ
- Remark: voltage, capacity, frequency, connection group and loss can be customized according to customer requirements

S11

Capacity

Rated voltage&Off-load tapping Vector
GroupSymbol
NO-load
loss(W)
Load loss(W) NO-load current(%) Short
circuit impedance(%)
H.V(kv) High pressure
Tap range(%)
L.V(kv)
30 kva 11 10.5
10 6.3
6
±5%
±2x2.5%
0.4
0.415
0.420
0.430
0.440

Dyn11
Yyn0
100 630/600 1.5 4
50 kva 130 910/870 1.3 4
63 kva 150 1090/1040 1.2 4
80 kva 180 1310/1250 1.2 4
100 kva 200 1580/1500 1.1 4
125 kva 240 1890/1800 1.1 4
160 kva 280 2310/2200 1 4
200 kva 340 2730/2600 1 4
250 kva 400 3200/3050 0.9 4
300 kva 480 3830/3650 0.9 4
400 kva 570 4520/4300 0.8 4
500 kva 680 5410/5150 0.8 4
630 kva 810 6200 0.6 4.5
800 kva 980 7500 0.6 4.5
1000 kva 1150 10300 0.6 4.5
1250 kva 1360 12000 0.5 4.5
1600 kva 1640 14500 0.5 4.5
2000 kva 1940 18300 0.4 5
2500 kva 2290 21200 0.4 5

 

10kV Dual-Winding On-Load (No Excitation Voltage Regulation) Fully Sealed Oil-Immersed Distribution Transformer

Capacity: 30~2000
Main Technical Parameters: Rated voltage 10kV, rated capacity ≤ 2000kVA, types 9, 10, and 11, dual-winding on-load (no excitation voltage regulation) fully sealed oil-immersed distribution transformer.
Main Applications: Power plants, substations, industrial and mining enterprises, user distribution stations, and other 10kV distribution systems.

 

Our company produces oil-immersed power transformers for 35kV and below, which have been developed based on the absorption of advanced domestic technology and tailored for the urban and rural power grid transformation in China. The performance indicators of these products exceed the requirements of GB/T6451-1999 "Technical Parameters and Requirements for Three-Phase Oil-Immersed Power Transformers," fully comply with the manufacturing standards of GB1094.1.2-1996, GB1094.3.5-2003 "Power Transformers," and the IEC-76 standards recommended by the International Electrotechnical Commission. These products feature low loss, low noise, and no core-lifting design, resulting in significant improvements in safety, reliability, and economy.

 

10kV Dual-Winding On-Load (No Excitation Voltage Regulation) Fully Sealed Oil-Immersed Power Transformer

Capacity: 800~2500
Main Technical Parameters: Rated voltage 10kV, rated capacity ≤ 2500kVA, 9 type, 10 type, 11 type, dual-winding on-load (no excitation voltage regulation) fully sealed oil-immersed power transformer.
Main Application Fields: Power plants, power stations, industrial and mining enterprises, user distribution stations, and other 10kV power systems.

 

Our company's oil-immersed power transformers for 35kV and below are developed based on the absorption of advanced domestic technologies and are specially designed for the urban and rural power grid renovation in China. The product performance exceeds the standards of GB/T6451-1999 Technical Parameters and Requirements for Three-Phase Oil-Immersed Power Transformers, fully complies with GB1094.1.2-1996, GB1094.3.5-2003 Power Transformers manufacturing standards, and the International Electrotechnical Commission (IEC) recommendation IEC-76. This product features low loss, low noise, and a core-lifting-free design, significantly enhancing safety, reliability, and economy.

 

The S11/S13/S20/S22 Series 10KV Fully Sealed Oil-Immersed Transformers are designed for AC systems operating at 50Hz/60Hz with rated working voltages of up to 20kV. These electrical transformers are ideal for power distribution in sectors like petroleum, metallurgy, chemical, textile, and light industries. Their robust design makes them suitable for dusty environments and demanding power substations.

 

  • High-Efficiency Core: The transformer core is made of high-permeability, grain-oriented cold-rolled silicon steel sheets. Featuring a new structure with fully mitered joints and stepped circular cross-sections, the core minimizes energy loss and noise.

 

  • Reliable Windings: The windings are designed with corrugated oil ducts and non-impregnated processes, secured with compression bands. High-voltage windings come with taps to adjust the voltage as required, with tap changers conveniently located on the tank lid for easy operation after power disconnection.

 

  • Safety Protection Devices: Models ranging from 30 to 2000kVA are equipped with pressure relief valves and optional gas relays with alarm and tripping terminals to enhance operational safety.

 

  • Advanced Oil Cooling System: The transformer features a corrugated wall tank with integrated cooling and "breathing" functions, eliminating the need for an oil conservator. The vacuum oil-filling process ensures no moisture or air contamination, enhancing the longevity of the AC transformer and reducing maintenance requirements.

10kv Oil immersed Transformer Standar & Certifaication


1. Standards: GB, IEC, GOST, EN, NF, ANSI/IEEE (customizable according to customer standards)

2. Certification: ISO,CE,IEC,SABS,COC,CSA,UL

3. Efficiency: The efficiency of an 10kV three-phase oil immersed transformer can exceed 99%, which can meet the European 2015/2014/548/EC ecodesign Tier 2 energy efficiency regulations.

4. Maintenance free: IP65 protection level, dustproof and moisture-proof, maintenance free, designed for a lifespan of over 25 years.

5. Environmental protection and sustainable development: FR3 vegetable oil can be selected.

6. Overload capacity: Copper coil 10kv transformer allows short-term overload to 150% of rated capacity for no more than 2 hours, but requires monitoring of oil temperature (≤ 95 ℃).

10KV Fully Sealed Three-phase Oil-immersed Power Distribution Transformer

Against the backdrop of global electricity demand growth, 10kV three-phase oil immersed transformers are widely used in rural power grids, industry, commerce, new energy, public facilities, and other fields. High reliability operational verification in over 50 countries and regions worldwide; Already sold to countries and regions such as East Asia, Central Asia, Southeast Asia, South Asia, etc

 

10kv Oil immersed Transformer Case show

10kv Oil Immersed Transformer

50-2500kVA/20(10)kV Low-Loss Oil Immersed Transformer(hermetically Sealed Oil Filled Transformer)

S11

● High voltage side voltage: 10kV, 20kV

● Low voltage Side voltage: 0.4kV

● Tapping Range: ±2×2.5%

● Transformer Vector Group: Yyn0 or Dyn11

● Tap Changer: NLTC or OLTC

● Certification: ISO9001, IEC60076, etc.

Note: More parameters can be customized according to customer requirements.

 

This S11-20(10)kV dual voltage oil immersed transformer is an upgraded version of the classic S9 series. Its biggest feature is that it can flexibly switch voltage (10kV or 20kV). This is particularly suitable for the needs of power grid upgrades. It can withstand more short-circuit current than the old S9 (capacity increased by 30%) and has lower noise during operation (reduced by about 5 decibels). It also adopts a fully sealed design that does not leak oil and is extremely energy-saving (20% energy-saving than S9).

 

S11-50~2500kVA/20(10)kV Whole-sealed Type Distribution Power Transformer Technical parameters

Rated

Capacity

(kVA)

Voltage

Marks

No-Load

Loss

(W)

On-Load

Loss

(W)

Short

cirait-z

(%)

No-Load

Cur

(%)

Weight(kg)

Size(mm)

Distance

(mm)

V

(kV)

Chng

(%)

V

(kV)

Wain w.t

Oil w.t

Ttl w.t

L·W·H

50

20

10

±2×2.5

0.4

Dyn11

Or

Yyn0

130

870

4

2

280

125

560

850×600×1260

400×400

80

180

1250

1.8

350

140

680

1030×680×1320

400×450

100

200

1500

1.6

470

155

800

1060×680×1370

400×450

125

240

1800

1.5

500

175

870

1110×700×1380

450×500

160

290

2200

1.4

520

190

980

1080×700×1430

550×550

200

330

2600

1.3

670

220

1200

1150×740×1500

550×550

250

400

3050

1.2

770

240

1310

1270×740×1510

550×550

315

480

3650

1.1

800

250

1400

1240×780×1550

550×550

400

570

4300

4.5

1

970

280

1600

1300×910×1580

660×660

500

680

5150

1

1100

315

1850

1400×870×1600

660×660

630

810

6200

0.9

1330

355

2200

1410×870×1700

660×660

800

980

7500

0.8

1590

430

2550

1480×920×1780

820×820

1000

1150

10300

0.7

1700

475

2800

1630×1090×1800

820×820

1250

1360

12000

0.6

1980

525

3200

1700×1130×1840

820×820

1600

1640

14500

0.6

2280

585

3800

1840×1250×1890

820×820

2000

2020

17820

0.5

2460

720

4600

1910×1330×1930

1000×1000

2500

2380

20700

0.5

2900

800

5200

1980×1380×1980

1070×1070

 

Note:

1. The diagonal load loss values ​​in the table below apply to products in the Dyn11 connection group.

2. If you need to know the technical parameters, dimensions and weight data of 10kV large-capacity distribution transformers, please contact us.

3. We can provide transformers with various voltage levels, short-circuit impedances and coupling methods according to user needs.

4. The weight and size data in the table are for reference only.

 

Application Scope

1. Normal use environment: altitude not exceeding 1000m; temperature range: -25℃-+40℃

2. Special environment: Altitude over 1000m; Temperature range: -45℃-+40℃

3. Relative humidity: ≤90% (+25℃)

4. Installation location: No corrosive gas, no obvious stains.

5. This product is suitable for industrial and agricultural lighting and power transmission.

 

10kv Oil immersed Transformer FAQ


What is an 10kV three-phase oil immersed transformer?

A three-phase oil immersed transformer is a power transformer that is cooled and insulated by insulating oil. It is designed for use in three-phase AC power systems and can convert high voltage electrical energy into low voltage (such as 10kV/400V). It is widely used in industrial, commercial, and power grid distribution.

 

What are the typical application scenarios?

*Voltage conversion of urban distribution network (10kV → 400V);

*Power distribution in industrial plants such as mines and petrochemicals;

*Grid connection of renewable energy power plants (such as wind farms);

*Hospitals, data centers, and other places that require high reliability power supply.

 

What is the rated capacity range?

The common capacity ranges from 25kVA to 10MVA, with the 100kVA to 2000kVA models of 10kV/400V being the most widely used, depending on the load requirements.

 

What is the difference in maintenance cycle between 10kV dry-type and oil immersed transformers?

Dry type: Dust removal inspection every 2-3 years; Oil immersed: Check the oil level, oil quality (pressure resistance value, acidity), sealing, and radiator cleaning once a year; Comprehensive oil sample testing every 3-5 years (such as medium loss and moisture content).

 

How to choose between three-phase oil immersed transformer and dry-type transformer?

-10kV oil immersed transformers are suitable for outdoor, high-capacity, and high load scenarios, with low cost but requiring regular maintenance;

-10kV dry-type transformer: used in indoor environments with high fire protection requirements (such as shopping malls and subways), maintenance free but expensive.

 

How to determine whether a transformer needs to change oil or filter oil?

-Oil quality testing: Regularly test the breakdown voltage (should be ≥ 30kV), water content (≤ 20ppm), and acid value of the oil;

-Cloudy oil color: The oil becomes darker or there is an increase in suspended matter;

-Decreased insulation performance: determined by withstand voltage test.

 

 

What are the reasons for the abnormal temperature rise during operation?

-Long term overload;

-Cooling system malfunction (fan/oil pump shutdown);

-Oil circuit blockage or insufficient oil volume;

-Internal short circuit or poor contact.

 

How to deal with oil leakage in oil immersed transformers?

-Slight oil leakage: tighten bolts or replace gaskets;

-Serious oil leakage: Stop immediately, drain the oil and repair or replace components;

 

What protective devices must be configured ?

*High voltage side: circuit breaker or fuse (with overcurrent/short-circuit protection);

*Body protection: gas relay, pressure relief valve, oil temperature gauge;

*System protection: lightning arrester (anti lightning impulse)

*Monitoring device: oil level gauge, online oil chromatography analyzer (high-end configuration).

 

 

What are the key points to pay attention to when installing ?

-Stable foundation, horizontal installation, avoiding tilting;

-Reserve sufficient heat dissipation space (such as at least 1.5 meters away from the wall);

-Grounding resistance ≤ 4 Ω;

-Check the oil level, sealing, and cleanliness of the casing.