Good Quality 500 KVA Three Phase Oil Filled Distribution Transformer Shipped To Thailand
Jul 08, 2025
Leave a message
Good Quality 500 KVA Three Phase Oil Filled Distribution Transformer Shipped To Thailand
Product Introduction
This 500 KVA transformer was delivered to Thailand in 2025. the rated power of the transformer is 500 KVA. the primary voltage of the transformer is 10 KV and secondary voltage is 0.4KV. Different from dry type transformer, it is a Liquid Dielectric Transformer, using mineral oil as cooling material. Our 400 KVA transformer was designed with advanced technology and adopts high quality material and components which result in reliable quality and long operation time.
Product: Oil Immersed distribution Transformer
Rated Power: Up to 5000 KVA
Primary Voltage: Up to 35 KV
PRODUCTS DESCRIPTION:
Three dimension Wound Core Oil Immersed Transformer Model Number: S13-M.RL
Rated Capacity: 500kVA
Winding Material: Copper
High Voltage (KV): 10
Low Voltage (KV): 0.4
Connection of the Transformer Winding : Dyn11 / Yyn0
No-Load loss (W) : 480
Load loss (W) : 5150
No-Load Current (%) : 0.16
Short circuit impedance:(%) : 4.0
Vector Group : 0.4
Temperature Rise: 65 ℃.
500 KVA Three Phase Oil Filled Distribution Transformer adopts the latest technology to significantly reduce both no-load loss (≤480W) and load loss (≤3650W). This 500 KVA Transformer features a compact structure, low temperature rise, and excellent heat dissipation capabilities, ensuring optimal performance in demanding environments. With a focus on safety and reliability, the design improvements and high-quality materials used in the 500 KVA Transformer extend its service life and reduce operational costs.
It is ideal for use in power supply and distribution systems with voltages below 35kV in substations, power stations, power plants, and industrial or mining enterprises. Designed to meet the diverse power distribution needs of various users, the 500 KVA Transformer offers a reliable, high efficiency solution for both urban and industrial settings.
500 KVA 10/0.4KV Transformer Tank

There are two common types of transformer tank:
1. Barrel type Tank: Generally used for small and medium-sized transformers
2. Bell type tank: for large transformers.
Packing and Delivery

| Place of Origin | China |
|---|---|
| Model Number | Oil immersed transformer |
| Type | Distribution Transformer |
| Standard | IEC60076 |
| Certificate | CSA SGS CE UL cUL |
| Rated Power | 500 KVA |
| Frequency | 50 HZ/60 HZ |
| Phase | Three |
| Cooling Type | ONAN |
| Primary Voltage | 11 KV |
| Secondary Voltage | 0.415 KV |
| Winding Material | Aluminum/Copper |
| Vector Group | Dyn11,Yyn0,Yzn11 |
| Oil preservation | Hermetically Sealed/ Conservator/ Free Breathing |
| Dielectric liquids | Mineral oil / Dimethyl Silicone/ FR3 oil |
| Coolers | corrugated wall or radiator |
| Impedance | 0.04 |
| Tap Changer | NLTC |
| Tapping Range | ±2*2.5% |
| Operating temperature | 40 To+180 |
| No Load Loss | 0.48KW |
| On Load Loss | 3.65KW |
| Accessories | Standard Configuration |
| Remarks | N/A |
Send Inquiry