S11 Series 6kV-35kV Power Transformer
Have questions? GNEE sales representatives are available for live chat now
Send E-mail: sales@gneeelectric.com
Tel: +8615824687445
S11 series power transformer adopts high quality material for copper winding, especially applying the new technology and new material for the coil insulation and active parts, thus the no-load and the load loss are obviously reduced, the performance and structure are more reliable and superior.
6KV, 10kV & 30kVA-2500kVA Power Transformer
Rated Capacity (kVA) | Voltage Combination | Connection Group Symbol | No-load Loss R(W) | Load Loss R(W)75℃ | Impedance Voltage (%) | No-load Current(%) | Active parts Weight(Kg) | Oil Weight(Kg) | Total Weight(Kg) | ||
(KV) High Voltage | Tapping Range of High Voltage | (KV)Low Voltage | |||||||||
30 | 66.31010.5 | ±5%±2×2.5% | 0.4 | Dyn11Yzn11Yyn0 | 100 | 630/600 | 4.0 | 2.8 | 178 | 78 | 355 |
50 | 130 | 910/870 | 2.5 | 240 | 92 | 415 | |||||
63 | 150 | 1090/1040 | 2.4 | 285 | 105 | 505 | |||||
80 | 180 | 1310/1250 | 2.2 | 330 | 110 | 540 | |||||
100 | 200 | 1580/1500 | 2.1 | 345 | 116 | 590 | |||||
125 | 240 | 1890/1800 | 2.0 | 415 | 135 | 705 | |||||
160 | 280 | 2310/2200 | 1.9 | 485 | 155 | 835 | |||||
200 | 340 | 2730/2600 | 1.8 | 582 | 168 | 965 | |||||
250 | 400 | 3200/3050 | 1.7 | 695 | 210 | 1135 | |||||
315 | 480 | 3830/3650 | 1.6 | 855 | 255 | 1520 | |||||
400 | 570 | 4520/4300 | 1.5 | 950 | 295 | 1590 | |||||
500 | 680 | 5410/5150 | 1.4 | 1150 | 320 | 1905 | |||||
630 | 810 | 6200 | 1.3 | 1500 | 435 | 2015 | |||||
800 | 980 | 7500 | 4.5 | 1.2 | 1910 | 760 | 3510 | ||||
1000 | 1150 | 10300 | 1.1 | 2125 | 880 | 3850 | |||||
1250 | 1360 | 12000 | 1.0 | 2605 | 960 | 4610 | |||||
1600 | 1640 | 14500 | 0.9 | 3125 | 1150 | 5420 | |||||
2000 | 1940 | 18300 | 5.0 | 0.4 | 2420 | 780 | 4200 | ||||
2500 | 2290 | 21200 | 0.4 | 2560 | 880 | 4680 |
Power tansformer Features
● Good Economic Performance
The no-load loss for S11 series power transformer products decreased 10.3% averagely, no-load current decreased 22.4% based on S9 series.
● Long Service Life
Transformer tank adopts hermetical structure, tank and tank cover can be connected by bolts or welded firmly, the transformer oil won't contact with air, so that extend the service life effectively.
● High Operation Reliability
Improve the relevant sealing parts for the tank, increase the reliability and advance the technical level to ensure the reliability of the seal.
● Small Installation Area
S11-M series power transformer tank uses the corrugated plate radiator. When the oil temperature changes, the corrugated plate will proceed thermal expansion, which can replace the role of the oil conservator. the corrugated plate tank has beautiful appearance, less occupied area.
Packaging&Shipping
Hot Tags: s11 series 6kv-35kv power transformer, China s11 series 6kv-35kv power transformer manufacturers, suppliers, factory, Substation Power Transformer, Pole Distribution Transformer, 200 kva distribution transformer, Dry Type Cast Resin Transformers, primary unit substation, small power transformer
You Might Also Like