33kV Fully Sealed Three-phase Low Loss Power Distribution Transformer

Nov 11, 2025

Leave a message

33kV three-phase oil-immersed transformers are widely used in rural power grids, industry, commerce, new energy, public facilities and other fields. They have been verified to have high reliability in more than 50 countries and regions around the world and have been sold to South Africa, Zimbabwe, Sudan, Kenya, Mozambique, Tanzania, Ethiopia, Nigeria, Namibia, Iraq, UAE, Saudi Arabia and other countries and regions.

 

33kv Oil immersed Transformer Technical Specifications


- Input voltage: 33kV
- Output voltage: 0.4kV 0.415kv 0.420kv 0.44kv
- Capacity: 30-25000 kva
- Frequency: 50HZ/60HZ
- Voltage regulation mode: NLTC (no Load tap changer)
- Remark: voltage, capacity, frequency, connection group and loss can be customized according to customer requirements

Capacity Rated voltage&Off-load tapping Vector
GroupSymbol
NO-load
loss(W)
Load loss(W) NO-load current Short
circuit impedance(%)
H.V(kv) High pressure
Tap range(%)
L.V(kv)
50 kva 33kV
35kV
38.5kV
±5%
±2x2.5%
0.4
0.416
0.42
0.44

Dyn11
Yyn0
210 1270/1210 2.0 6.5
100 kva 290 2120/2020 1.8 6.5
150 kva 340 2500/2380 1.7 6.5
160 kva 360 2970/2380 1.6 6.5
200 kva 430 3500/3330 1.5 6.5
250 kva 510 4160/3960 1.4 6.5
300 kva 610 5010/4770 1.4 6.5
400 kva 730 5050/5760 1.3 6.5
500 kva 860 7280/6930 1.2 6.5
600 kva 1040 8280 1.1 6.5
750 kva 1230 9900 1.0 6.5
1000 kva 1440 12150 1.0 6.5
1250 kva 1760 14670 0.9 6.5
1500 kva 2120 17550 0.8 6.5
2000 kva 2490 20740 0.8 6.5
2500 kva 2950 24420 0.8 6.5
3000 kva 3510 29050 0.7 6.5
4000 kva 4200 34940 0.7 6.5
5000 kva 4960 41160 0.7 6.5

 

Type: 33kV three-phase transformer

These types of transformers have the same principle, but different structures, and different types of transformers have different applications.

33kV three-phase oil-immersed transformer (rated voltage 6kV-35kV)

33kV pole-mounted three-phase oil-immersed transformer (rated voltage 2.4kv-34.5kv)

 

33kv Oil immersed Transformer Case show

10KV 400KVA Three Phase Low Loss Distribution Transformer

The 10kV 400kVA Three-Phase Low Loss Distribution Transformer is a high-efficiency power solution designed for demanding urban and industrial applications. Utilizing advanced oil-immersed technology, it minimizes no-load and load losses, enhancing energy savings while ensuring superior thermal stability. Its core is crafted from high-quality cold-rolled silicon steel, reducing magnetic losses and boosting overall efficiency. The transformer features a fully sealed oil tank that prevents insulation degradation, extending its operational lifespan. With precise voltage regulation and low noise operation, it is an ideal choice for urban substations, commercial centers, and specialized industrial networks, delivering consistent and reliable power performance.

info-848-593

 

33kv Oil immersed Transformer FAQ


What is an 33kV three-phase oil immersed transformer?

A three-phase oil immersed transformer is a power transformer that is cooled and insulated by insulating oil. It is designed for use in three-phase AC power systems and can convert high voltage electrical energy into low voltage (such as 33kV/400V). It is widely used in industrial, commercial, and power grid distribution.

 

What is a 33KV transformer?

33KV power transformers are commonly used in power transmission substations to step-down high-voltage transmission to distribution levels. 11KV transformers are more often used in distribution substations and on utility poles to further step-down voltage for supplying end users.

 

What are the typical application scenarios ?

*Voltage conversion of urban distribution network (33kV → 400V);

*Power distribution in industrial plants such as mines and petrochemicals;

*Grid connection of renewable energy power plants (such as wind farms);

*Hospitals, data centers, and other places that require high reliability power supply.

 

What is the rated capacity range ?

The common capacity ranges from 25kVA to 10MVA, with the 100kVA to 2000kVA models of 33kV/400V being the most widely used, depending on the load requirements.

 

What is the difference in maintenance cycle between 33kV dry-type and oil immersed transformers?

Dry type: Dust removal inspection every 2-3 years; Oil immersed: Check the oil level, oil quality (pressure resistance value, acidity), sealing, and radiator cleaning once a year; Comprehensive oil sample testing every 3-5 years (such as medium loss and moisture content).

 

How to choose between three-phase oil immersed transformer and dry-type transformer?

-33kV oil immersed transformers are suitable for outdoor, high-capacity, and high load scenarios, with low cost but requiring regular maintenance;

-33kV dry-type transformer: used in indoor environments with high fire protection requirements (such as shopping malls and subways), maintenance free but expensive.

 

How to determine whether a transformer needs to change oil or filter oil?

-Oil quality testing: Regularly test the breakdown voltage (should be ≥ 30kV), water content (≤ 20ppm), and acid value of the oil;

-Cloudy oil color: The oil becomes darker or there is an increase in suspended matter;

-Decreased insulation performance: determined by withstand voltage test.

 

 

What are the reasons for the abnormal temperature rise during operation?

-Long term overload;

-Cooling system malfunction (fan/oil pump shutdown);

-Oil circuit blockage or insufficient oil volume;

-Internal short circuit or poor contact.

 

How to deal with oil leakage in oil immersed transformers?

-Slight oil leakage: tighten bolts or replace gaskets;

-Serious oil leakage: Stop immediately, drain the oil and repair or replace components;

 

What protective devices must be configured for Q9?

*High voltage side: circuit breaker or fuse (with overcurrent/short-circuit protection);

*Body protection: gas relay, pressure relief valve, oil temperature gauge;

*System protection: lightning arrester (anti lightning impulse)

*Monitoring device: oil level gauge, online oil chromatography analyzer (high-end configuration).

 

 

What are the key points to pay attention to when installing Q10?

-Stable foundation, horizontal installation, avoiding tilting;

-Reserve sufficient heat dissipation space (such as at least 1.5 meters away from the wall);

-Grounding resistance ≤ 4 Ω;

-Check the oil level, sealing, and cleanliness of the casing.