630kVA 10kV/0.4kV Oil Immersed Distribution Transformer
Jun 15, 2026
Leave a message
Document Index
What Are the Full Technical Parameters of a 630kVA 10kV Transformer?
What Is the Loss of a 630kVA Transformer?
What Is the Impedance Voltage of a 630kVA Transformer?
What Is the Oil Capacity of a 630kVA Transformer?
How Much Does a 630kVA Transformer Weigh?
What Are the Dimensions of a 630kVA Transformer?
Which Applications Commonly Use 630kVA Transformers?
How does a fully sealed oil conservator / oil tank work in a 630kVA transformer?
What is the vector group Dyn11 in 630kVA transformers, and why is it important?
What is the impedance voltage of a 630kVA transformer?
What Is the Difference Between S11 and S13 630kVA Transformers?
Frequently Asked Questions (FAQ)



The 630kVA 10kV/0.4kV oil immersed transformer is one of the most widely used distribution transformers in commercial, industrial, utility, renewable energy, and infrastructure projects. It is commonly manufactured in S11, S13, and energy-efficient transformer series and is designed to step down medium-voltage power networks to low-voltage distribution systems.
A standard 630kVA oil-filled transformer complies with IEC 60076, GB 1094, IEEE C57, and other international standards. It features low no-load loss, stable impedance voltage, reliable insulation performance, and long service life. Typical applications include factories, solar power plants, EV charging stations, commercial buildings, hospitals, mining operations, and rural electrification projects.
What Are the Full Technical Parameters of a 630kVA 10kV Transformer?
The following table shows the typical specifications of a 630kVA oil immersed distribution transformer.
| Item | Standard Value |
|---|---|
| Rated Capacity | 630kVA |
| High Voltage | 10kV / 11kV |
| Low Voltage | 0.4kV |
| Frequency | 50Hz / 60Hz |
| Phase | Three Phase |
| Cooling Method | ONAN |
| Vector Group | Dyn11 |
| Tap Changer | ±2×2.5% or ±5% Off-Circuit |
| Impedance Voltage | 4%–6% |
| No-Load Current | ≤1.0% |
| Insulation Class | Class A |
| Transformer Oil | Mineral Oil / FR3 Ester Oil |
| Standard | IEC 60076 / GB 1094 |
| Protection Degree | IP23-IP54 (Optional) |
Need a quote with your exact voltage, loss limits, and local certification?
Request a customized 630kVA transformer specification sheet (S11/S13/ester oil/sealed type) and receive a firm FOB quotation within 24 hours.
What Is the Loss of a 630kVA Transformer?
Transformer losses directly affect operating costs and energy efficiency.
| Transformer Type | No-Load Loss | Load Loss |
|---|---|---|
| S11-630kVA | 980W | 6200W |
| S13-630kVA | 760W | 5960W |
| Energy Efficient Type | 600–700W | 5600–5900W |
The S13 series can reduce no-load losses by approximately 20–30% compared with conventional S11 transformers, helping users lower electricity consumption throughout the transformer's service life.
What Is the Oil Capacity of a 630kVA 10kV/0.4kV oil immersed transformer?
The oil quantity depends on the design, manufacturer, cooling system, and efficiency class.
| Transformer Type | Oil Capacity |
|---|---|
| Standard 630kVA | 500–650 Liters |
| Conservator Type | 550–700 Liters |
| Fully Sealed Type | 500–650 Liters |
The insulating oil performs three critical functions:
- Electrical insulation
- Heat dissipation
- Arc suppression
Regular oil testing helps ensure long-term transformer reliability.
How Much Does a 630kVA 10kV/0.4kV oil immersed transformer Weigh?
Transformer weight varies according to design standards and materials.
| Component | Weight |
|---|---|
| Active Part | 1200–1600 kg |
| Transformer Oil | 450–650 kg |
| Tank & Accessories | 600–900 kg |
| Total Weight | 2200–3200 kg |
Transportation planning should always consider both shipping weight and lifting requirements.
What Are the Dimensions of a 630kVA Transformer?
| Dimension | Approximate Value |
|---|---|
| Length | 1500–1900 mm |
| Width | 900–1200 mm |
| Height | 1400–1800 mm |
Actual dimensions may vary depending on voltage level, cooling structure, and customer specifications.
Which Applications Commonly Use 630kVA 10kV/0.4kV oil immersed transformer?





Commercial Buildings
A 630kVA oil transformer typically powers a 10,000–15,000 m² commercial complex and costs 30–40% less than dry type for outdoor or basement substations.
Industrial Plants
It handles motor‑heavy loads with 150% short‑term overload capacity while sitting outdoors, saving valuable factory floor space.
Solar Power Projects
The 630kVA unit matches 600–700 kWp solar arrays and its sealed oil construction withstands daily temperature swings and UV exposure in PV farms.
EV Charging Stations
One 630kVA oil transformer supports 10–15 DC fast chargers and manages rapid daily load cycling better than dry type due to superior oil heat dissipation.
Rural Electrification
Pole‑mounted 630kVA sealed oil transformers supply 300–500 households or irrigation pumps, needing no building and only 5‑year maintenance intervals.
How does a fully sealed oil conservator / oil tank work in a 630kVA 10kV/0.4kV oil immersed transformer?
The fully sealed capsule-type oil conservator prevents oxidation and moisture ingress into transformer oil.
A flexible rubber capsule is installed inside the conservator tank. As transformer oil expands during operation, the capsule compresses. When oil cools and contracts, the capsule expands back. This completely isolates the oil from ambient air.
- Prevents oxidation
- Prevents moisture absorption
- Reduces maintenance requirements
- Extends transformer service life
This construction is standard on many modern S13-M fully sealed transformers.
What is the vector group Dyn11 in 630kVA transformers, and why is it important?
Dyn11 is the most common vector group for 630kVA distribution transformers.
- D = High-voltage winding connected in Delta
- y = Low-voltage winding connected in Star (Wye)
- n = Neutral point available on LV side
- 11 = 30° phase displacement
Benefits of Dyn11:
- Reduces third harmonic currents
- Provides a stable neutral point
- Allows parallel operation
- Improves power quality
What is the impedance voltage of a 630kVA 10kV/0.4kV oil immersed transformer?
The standard impedance voltage for a 630kVA 10kV/0.4kV transformer is typically 4.0% or 4.5%.
Impedance voltage represents the percentage of rated primary voltage required to produce full-load current when the secondary winding is short-circuited.
With 4% impedance voltage, the theoretical short-circuit current at LV terminals is approximately 25 times rated current.
What Is the Difference Between S11 and S13 630kVA Transformers?
| Parameter | S11 | S13 |
|---|---|---|
| No-Load Loss | Higher | Lower |
| Energy Efficiency | Standard | High |
| Operating Cost | Higher | Lower |
| Initial Investment | Lower | Higher |
| Lifecycle Cost | Higher | Lower |


For projects with continuous operation and long service life, S13 transformers generally provide better economic returns through reduced energy losses.
Ready to order for your EV station, solar farm, or industrial project?
We supply 630kVA oil-immersed transformers with IEC/CE/UL certificates, copper windings as standard, and fast delivery to Africa, Southeast Asia, Middle East, and Europe.
Send your inquiry (quantity, voltage, destination port) to get a volume discount and lead time in one business day
















FAQ
Q1: What is the difference between S11 and S13 630kVA transformers?
A: S13 reduces no-load loss by approximately 27–30% while providing improved energy efficiency with slightly higher initial investment.
Q2: What is the oil capacity of a 630kVA transformer?
A: Typically 430–650 kg (approximately 480–730 liters), depending on design and manufacturer.
Q3: Can a 630kVA transformer handle EV charging station loads?
A: Yes. It can support approximately 10–15 DC fast chargers depending on charger power and demand diversity.
Q4: What is the full load current of a 630kVA 10kV/0.4kV transformer?
A: LV side ≈ 909A. HV side ≈ 36.4A.
Q5: How many houses can a 630kVA transformer supply?
A: Approximately 250–300 homes under average demand conditions, or 400–500 homes when diversity factors are applied.
Q6: What cooling method is used in 630kVA oil-immersed transformers?
A: ONAN (Oil Natural Air Natural).
Q7: What is the typical lifespan of a 630kVA oil-immersed transformer?
A: Typically 25–30+ years with proper maintenance.
Q8: Can 630kVA transformers be used for step-up applications?
A: Yes. They are widely used in solar power plants, wind farms, and battery energy storage systems for grid integration.